    Experimental investigation of a ground coupled desiccant assisted air conditioning system during winter mode
    (Curran Associates, Inc., 2018-07) ;
    Air conditioning for residential as well as non-residential applications is increasing due to various reasons. Most commonly, income growth in developing and emerging countries, climate change and increased energy building standards are indicated as reasons causing growing demand for air conditioning. Currently, most air conditioning systems are based on conditioning supply air by cooling outside air below dew point temperature, relying on a vapor compression chiller. Due to high energy demands of such systems, alternative air conditioning concepts are investigated. The advantages of desiccant assisted systems in summer mode are well-established in literature, especially in terms of performance analyses in hot and humid regions when air has to be cooled and dehumidified. Even though winter mode is an essential part of the full year operation, especially for heating dominated regions, winter mode as well as full year operation are addressed only in few studies. A further comfort aspect is the increase of moisture level of supply air against the background of dry air conditions in air conditioned buildings without additional humidification systems during winter. Within a desiccant assisted system, moisture recovery by means of the existing hygroscopic materials is possible; the related energy demand is limited to auxiliary energies. In the framework of a research project at Hamburg University of Technology the combination of an open cycle desiccant assisted air conditioning system and borehole heat exchangers is investigated experimentally by means of a pilot plant in full year operation. During summer mode, dehumidification and cooling are separated within the process. Therefore, heat sinks working on higher temperature levels compared to conventional systems can be used. Furthermore, surface heat exchangers removing sensible loads from the conditioned space enable an energy efficient operation of the overall system; volume flow rates of supply and extract air can be reduced to minimal air exchange rate required by hygienic reasons. A shallow geothermal system with borehole heat exchanger is used as heat sink. To make use of this subsystem during full year operation and with regard to an equalized energy balance of the soil, a ground coupled heat pump is integrated for heating purposes in winter mode. The objective of this work is to analyze the potential of the geothermal system and to investigate the energy efficiency of the overall system, evaluating data measured during winter 2017 for a temperate climate region. Different reference systems are defined to evaluate the performance of the investigated system. Compared with a system relying on isothermal humidification, the electrical energy demand is reduced by up to 68% for humidification. Furthermore, combined heat and moisture recovery is investigated as well as the performance of the enthalpy wheel based on LiCl. An average moisture recovery efficiency of 0.75 is achieved. Besides the energetic system evaluation, measured data regarding the soil temperature and thermal comfort are presented.
    Publicationtype: Conference Paper
      188  39
  • Some of the metrics are blocked by your 
    Item type:Publication, Access status: Restricted ,
    Three-fluid heat exchanger as evaporator in multi-source heat pumps with viable options for alternative defrosting methods
    (Curran Associates, Inc., 2018-07) ; ;
    Three-fluid evaporators can be used for multi-source heat pumps to keep refrigeration circuits simple in design since it avoids the usage of a second or more evaporators. In this work a defrosting control design is presented with a lowered electrical energy demand compared to the standard procedure of reverse cycle defrosting with 4-wayvalves. Objective of this new defrosting concept is to develop a fully autonomous defrosting strategy. The two heat sources allow direct thermal communication of an air source and a second heat source based on a hydronic circuit with the evaporating refrigerant. The proposed defrosting strategy is based on the combination of natural circulation defrosting and a hybrid defrosting strategy which allows defrosting during operation but at the expense of significantly higher heat source inlet temperatures above 0 °C of the hydronic-based heat source. The nominal operation and heat transfer from ambient air will be stopped thus the evaporation temperature can be increased up to defrosting temperature levels. Finally the two concepts of the de-facto standard reverse cycle defrosting and this new hybrid defrosting strategy are compared in their economic efficiency when designed for a single heat pumps.
    Publicationtype: Conference Paper
      215  61
  • Some of the metrics are blocked by your 
    Item type:Publication, Access status: Restricted ,
    Investigation of the pressure drop in refrigerant pipes of an R744 automotive air conditioning system
    (Curran Associates, Inc., 2018-07) ;
    This paper presents a test rig to measure the pressure drop of the refrigerant R744 (CO2) in refrigerant pipes of an automotive air conditioning system. The experimental layout is basically a cooling cycle. In a measurement section, arbitrary shaped pipes of an automotive air conditioning system can be installed. As boundary conditions mass flow, pressure and enthalpy of the refrigerant at the inlet are independently adjustable to values that cover the whole operating range of an R744 automotive air conditioning system. In addition to the experimental investigations, a numerical analysis with CFD software is conducted. The results are compared with the test rig results to validate the numerical model. Finally, the impact of the refrigerant pipes pressure drop on system behavior is analyzed with a comparison of two models of an R744 air conditioning system in Modelica. One model includes the resistance coefficients based on experimental data and the other model uses simplified state of the art pipe models.
    Publicationtype: Conference Paper
      220  39